国标铜汇流排流量计中普通铜汇流排载流量的计算方法: 40℃时铜汇流排载流量=行宽*厚度系数12108654系数201816141312双层铜汇流排[40℃] = 1.56-1.58 [40℃] = 2个单层铜母线4层铜母线[40℃] =单层铜母线* 2.45(最好用异形母线代替)铜母线[40℃] =铜母线以[25℃] * 0.85为例,求出TMY100 * 10的载流量为: 单层: 100 * 18 = 1800(A)[手册中的1860A];双层: 2(TMY100 * 10): 1860 * 1.58 = 2940(A); [检查手册是2942A];三层: 3(TMY100 * 10)载流量为: 1860 * 2 = 3720(A)[检查手册为3780A]以上所有计算均与手册数据相符. 常用铜排尺寸和载流量表矩形铜排铜母线段35°C 25°C 40°C(A)垂直(A)水平(A)垂直(A)水平(A)垂直(A)15×317618520021020×323324526127525 ×328530032334030×439441545147540×440442552255040×545247555158850×555658572176050×661765079784060×673177094099060×88589001101116060×1096010101230129580×693010101195130080×8106011551361148080×101190129515311665100×61160126015571592100×81310142516741850100×101470159518652025120×81530167519402110120×1016851830215223402(60×6)11261185145215302(60×8)14601480150316002(60×10 )16801170214022502(80×6)13201433170518552(80×8)16511795211725152(80×10)19502120257527352(100×6)15641700200021702(100×8)19302100247026902(100×10)23202500293531852(120×8)21402330275029952(120×10)2615284033303620铜导体的载流量(35℃)截面(mm2)11.52.54610162535507095载流量(A)